New Castle County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 4492 Orchard Rd

Approved

Filed Jun 8, 2024 by Logan Nguyen, Northstar Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Jun 8, 2024
Assembly type
RP
Serial number
A678044
Size
3/4
Test gauge serial
G-1831
Gauge calibration date
Dec 13, 2023
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-10-01228
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4492 Orchard Rd
Owner: Jordan Ellery
Parcel 003-10-01228