New Castle County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Hilltop Apartments

Approved

Filed Dec 20, 2023 by Rowan Hollins, Northstar Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Dec 20, 2023
Assembly type
RP
Serial number
K265679
Size
2
Test gauge serial
G-9977
Gauge calibration date
Apr 17, 2023
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-96-01322
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1385 Stone Gate Ln
Owner: Okafor Holdings LLC
Parcel 003-96-01322