Backflow assembly test · 4492 Orchard Rd
ApprovedFiled Jul 14, 2025 by Rowan Hollins, Northstar Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Jul 14, 2025
- Assembly type
- RP
- Serial number
- A678044
- Size
- 3/4
- Test gauge serial
- G-3608
- Gauge calibration date
- Sep 22, 2024
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 1.5 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 003-10-01228
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.