Backflow assembly test · Main Street Car Wash

Approved

Filed Oct 28, 2025 by Blake Vance, Valley Backflow Testing · filed from phone

Report

Date of service
Oct 28, 2025
Assembly type
RP
Serial number
A908430
Size
2
Test gauge serial
G-8864
Gauge calibration date
Nov 30, 2024
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
1.5 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-63-01170
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1321 Cedar Hollow Ln
Owner: Wexler Holdings LLC
Parcel 003-63-01170