Backflow assembly test · 5158 Orchard Dr

Approved

Filed Jan 11, 2026 by Rowan Hollins, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Jan 11, 2026
Assembly type
RP
Serial number
B294544
Size
3/4
Test gauge serial
G-2877
Gauge calibration date
Jul 10, 2025
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-20-01094
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5158 Orchard Dr
Owner: Avery Whitcomb
Parcel 003-20-01094