Backflow assembly test · 9882 Pine Knoll Rd

Approved

Filed May 6, 2026 by Rowan Hollins, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
May 6, 2026
Assembly type
DC
Serial number
A701665
Size
1
Test gauge serial
G-3381
Gauge calibration date
Jun 1, 2025
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-27-01161
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9882 Pine Knoll Rd
Owner: Logan Wexler
Parcel 003-27-01161