New Castle County, DEReports, deadlines and notices in one place
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 5312 Hickory Way

Approved

Filed Mar 9, 2026 by Drew Lindqvist, Ridge Backflow Testing · filed from phone

Report

Date of service
Mar 9, 2026
Assembly type
RP
Serial number
K520888
Size
1
Test gauge serial
G-8235
Gauge calibration date
Jun 5, 2025
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 003-84-01343
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5312 Hickory Way
Owner: Cameron Ashby
Parcel 003-84-01343