New Castle County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Riverside Bakery

Approved

Filed Aug 3, 2024 by Rowan Hollins, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Aug 3, 2024
Assembly type
RP
Serial number
K104064
Size
1 1/2
Test gauge serial
G-8019
Gauge calibration date
Jun 16, 2024
Check valve 1
5.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-15-01115
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8732 Cedar Hollow Trl
Owner: Vance Holdings LLC
Parcel 003-15-01115