← Backflow review queue
Backflow assembly test · 2268 Mill Creek Dr
ApprovedFiled May 21, 2025 by Parker Ramirez, Heritage Plumbing & Backflow · filed from phone
Report
- Date of service
- May 21, 2025
- Assembly type
- PVB
- Serial number
- W535606
- Size
- 1
- Test gauge serial
- G-6207
- Gauge calibration date
- Nov 22, 2024
- Check valve 1
- 8.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 005-36-01023
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2268 Mill Creek Dr
Owner: Morgan Marsh
Parcel 005-36-01023