Backflow assembly test · 1428 Laurel Ln
ApprovedFiled Oct 18, 2026 by Casey Pruitt, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Oct 18, 2026
- Assembly type
- RP
- Serial number
- A580602
- Size
- 3/4
- Test gauge serial
- G-9581
- Gauge calibration date
- Oct 28, 2025
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 3.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Pruitt, current on the service date
- All required fields present
- Address matches parcel 005-46-01244
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.