Backflow assembly test · 196 Turkey Hill Dr
ApprovedFiled Jul 15, 2026 by Casey Pruitt, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 15, 2026
- Assembly type
- PVB
- Serial number
- A515574
- Size
- 3/4
- Test gauge serial
- G-9977
- Gauge calibration date
- Mar 20, 2025
- Check valve 1
- 0.9 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.5 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 005-73-01103
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
196 Turkey Hill Dr
Owner: Jamie Marsh
Parcel 005-73-01103