Backflow assembly test · 9724 Turkey Hill Dr

Approved

Filed Mar 2, 2024 by Casey Pruitt, Ridge Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Mar 2, 2024
Assembly type
RP
Serial number
K643216
Size
3/4
Test gauge serial
G-1246
Gauge calibration date
Jul 9, 2023
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 005-78-01329
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.