← Backflow review queue
Backflow assembly test · 9724 Turkey Hill Dr
ApprovedFiled Mar 13, 2025 by Shawn Hollins, Heritage Plumbing & Backflow · filed from phone
Report
- Date of service
- Mar 13, 2025
- Assembly type
- RP
- Serial number
- K643216
- Size
- 3/4
- Test gauge serial
- G-7026
- Gauge calibration date
- Nov 3, 2024
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 4.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Shawn Hollins, current on the service date
- All required fields present
- Address matches parcel 005-78-01329
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
9724 Turkey Hill Dr
Owner: Morgan Pruitt
Parcel 005-78-01329