Backflow assembly test · 9724 Turkey Hill Dr
ApprovedFiled Mar 3, 2026 by Parker Ramirez, Heritage Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Mar 3, 2026
- Assembly type
- RP
- Serial number
- K643216
- Size
- 3/4
- Test gauge serial
- G-6725
- Gauge calibration date
- Jun 12, 2025
- Check valve 1
- 8.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Ramirez, current on the service date
- All required fields present
- Address matches parcel 005-78-01329
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9724 Turkey Hill Dr
Owner: Morgan Pruitt
Parcel 005-78-01329