Sussex County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 1865 Pine Knoll Way

Approved

Filed Apr 4, 2026 by Alex Ellery, Patriot Backflow Testing · filed from phone

Report

Date of service
Apr 4, 2026
Assembly type
RP
Serial number
W766496
Size
1
Test gauge serial
G-2324
Gauge calibration date
Oct 24, 2025
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-15-01089
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1865 Pine Knoll Way
Owner: Sam Nguyen
Parcel 005-15-01089