Sussex County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2058 Spring Branch Way

Approved

Filed Jul 31, 2025 by Casey Pruitt, Ridge Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Jul 31, 2025
Assembly type
PVB
Serial number
W951433
Size
1
Test gauge serial
G-4513
Gauge calibration date
Mar 10, 2025
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-30-01296
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2058 Spring Branch Way
Owner: Taylor Ramirez
Parcel 005-30-01296