Alachua County, FLReports, deadlines and notices in one place
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Blue Heron Bakery

Approved

Filed Sep 7, 2026 by Reese Danner, Heritage Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Sep 7, 2026
Assembly type
RP
Serial number
W727526
Size
1
Test gauge serial
G-2245
Gauge calibration date
Jan 15, 2026
Check valve 1
4.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Danner, current on the service date
  • All required fields present
  • Address matches parcel 001-91-01198
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

6196 Quarry Way
Owner: Okafor Holdings LLC
Parcel 001-91-01198