← Backflow review queue
Backflow assembly test · 7230 Stone Gate Dr
ApprovedFiled Sep 27, 2025 by Morgan Fairley, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Sep 27, 2025
- Assembly type
- DC
- Serial number
- B870186
- Size
- 3/4
- Test gauge serial
- G-8109
- Gauge calibration date
- Feb 11, 2025
- Check valve 1
- 7.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-35-01120
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7230 Stone Gate Dr
Owner: Emerson Calloway
Parcel 001-35-01120