Backflow assembly test · 5942 Ridgeview Ct
ApprovedFiled Apr 3, 2026 by Morgan Fairley, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Apr 3, 2026
- Assembly type
- RP
- Serial number
- B622647
- Size
- 1
- Test gauge serial
- G-9093
- Gauge calibration date
- Jan 28, 2026
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 4 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-13-01045
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
5942 Ridgeview Ct
Owner: Shawn Nguyen
Parcel 001-13-01045