Backflow assembly test · 4342 Hickory Dr

Approved

Filed Nov 19, 2024 by Blake Okafor, Heritage Plumbing & Backflow · filed from phone

Report

Date of service
Nov 19, 2024
Assembly type
RP
Serial number
K828492
Size
3/4
Test gauge serial
G-1520
Gauge calibration date
Jul 31, 2024
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-19-01266
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

4342 Hickory Dr
Owner: Casey Ashby
Parcel 001-19-01266