Alachua County, FLCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 1937 Fox Run Rd

Approved

Filed May 13, 2024 by Logan Marsh, Evergreen Backflow Testing · filed from phone

Report

Date of service
May 13, 2024
Assembly type
RP
Serial number
Z343134
Size
1
Test gauge serial
G-9174
Gauge calibration date
Aug 7, 2023
Check valve 1
0.1 psid
Check valve 1 closed tight
No
Check valve 2
3.4 psid
Relief valve opened at
4.1 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-75-01007
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

1937 Fox Run Rd
Owner: Emerson Marsh
Parcel 001-75-01007