Backflow assembly test · 1937 Fox Run Rd

Approved

Filed Apr 30, 2025 by Rowan Harlow, Evergreen Backflow Testing · filed from phone

Report

Date of service
Apr 30, 2025
Assembly type
RP
Serial number
Z343134
Size
1
Test gauge serial
G-5197
Gauge calibration date
Jan 11, 2025
Check valve 1
3.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-75-01007
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.