Alachua County, FLCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Hilltop Animal Hospital

Approved

Filed Dec 8, 2025 by Logan Marsh, Evergreen Backflow Testing · filed from phone

Report

Date of service
Dec 8, 2025
Assembly type
RP
Serial number
A261020
Size
2
Test gauge serial
G-8213
Gauge calibration date
Sep 9, 2025
Check valve 1
6.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-12-01125
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

6974 Mill Creek Way
Owner: Harlow Holdings LLC
Parcel 001-12-01125