Backflow assembly test · 3111 Spring Branch Dr
Needs reviewFiled Nov 17, 2026 by Reese Danner, Heritage Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 17, 2026
- Assembly type
- RP
- Serial number
- K496743
- Size
- 1
- Test gauge serial
- G-3975
- Gauge calibration date
- Oct 24, 2025
- Check valve 1
- 0.2 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 2.4 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-13-01148
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.