Backflow assembly test · Main Street Animal Hospital
ApprovedFiled Jun 9, 2024 by Shawn Hollins, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Jun 9, 2024
- Assembly type
- RP
- Serial number
- A409503
- Size
- 2
- Test gauge serial
- G-6804
- Gauge calibration date
- Aug 15, 2023
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.5 psid
- Relief valve opened at
- 3.2 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-68-01000
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9458 Fox Run Dr
Owner: Okafor Holdings LLC
Parcel 009-68-01000