← Backflow review queue
Backflow assembly test · Crossroads Animal Hospital
ApprovedFiled Jul 5, 2025 by Shawn Pruitt, Keystone Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Jul 5, 2025
- Assembly type
- RP
- Serial number
- Z564962
- Size
- 1 1/2
- Test gauge serial
- G-7452
- Gauge calibration date
- Nov 7, 2024
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Shawn Pruitt, current on the service date
- All required fields present
- Address matches parcel 009-22-01112
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1926 Spring Branch Ct
Owner: Wexler Holdings LLC
Parcel 009-22-01112