Backflow assembly test · Corner Market

Approved

Filed Mar 13, 2026 by Shawn Pruitt, Keystone Backflow Testing · filed from phone

Report

Date of service
Mar 13, 2026
Assembly type
RP
Serial number
B603160
Size
4
Test gauge serial
G-6985
Gauge calibration date
Dec 29, 2024
Check valve 1
0.8 psid
Check valve 1 closed tight
No
Check valve 2
3.2 psid
Relief valve opened at
3 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-69-01291
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

949 Quarry Ln
Owner: Stroud Holdings LLC
Parcel 009-69-01291