Backflow assembly test · Corner Pizza

Approved

Filed Oct 11, 2026 by Quinn Fairley, Lakeside Backflow Testing · filed from phone

Report

Date of service
Oct 11, 2026
Assembly type
RP
Serial number
W339570
Size
4
Test gauge serial
G-8860
Gauge calibration date
Feb 19, 2026
Check valve 1
6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-44-01311
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.