Brevard County, FLCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 4225 Stone Gate Way

Filed Nov 24, 2026 by Sam Nguyen, Keystone Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Nov 24, 2026
Assembly type
RP
Serial number
B238727
Size
1
Test gauge serial
G-5639
Gauge calibration date
Jan 1, 2026
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
1.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-20-01152
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Property

4225 Stone Gate Way
Owner: Avery Lindqvist
Parcel 009-20-01152