Backflow assembly test · 6771 Cedar Hollow Dr

Approved

Filed Jul 27, 2024 by Shawn Pruitt, Keystone Backflow Testing · filed from phone

Report

Date of service
Jul 27, 2024
Assembly type
RP
Serial number
K348772
Size
1
Test gauge serial
G-5920
Gauge calibration date
Oct 11, 2023
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-52-01114
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.