Brevard County, FLCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 6771 Cedar Hollow Dr

Approved

Filed Jul 13, 2025 by Quinn Fairley, Lakeside Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Jul 13, 2025
Assembly type
RP
Serial number
K348772
Size
1
Test gauge serial
G-3815
Gauge calibration date
Jun 1, 2024
Check valve 1
0.4 psid
Check valve 1 closed tight
No
Check valve 2
1.5 psid
Relief valve opened at
3.1 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-52-01114
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6771 Cedar Hollow Dr
Owner: Parker Okafor
Parcel 009-52-01114