Brevard County, FLReports, deadlines and notices in one place
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 8807 Laurel Way

Approved

Filed Oct 31, 2025 by Shawn Kessler, Valley Plumbing & Backflow · filed from phone

Report

Date of service
Oct 31, 2025
Assembly type
RP
Serial number
W801203
Size
3/4
Test gauge serial
G-5727
Gauge calibration date
Jan 6, 2025
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Shawn Kessler, current on the service date
  • All required fields present
  • Address matches parcel 009-85-01081
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8807 Laurel Way
Owner: Quinn Calloway
Parcel 009-85-01081