Brevard County, FLCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 5850 Mill Creek Rd

Approved

Filed Nov 1, 2025 by Sam Nguyen, Keystone Backflow Testing · filed from phone

Report

Date of service
Nov 1, 2025
Assembly type
RP
Serial number
W125766
Size
3/4
Test gauge serial
G-2332
Gauge calibration date
Feb 12, 2025
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-94-01084
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

5850 Mill Creek Rd
Owner: Logan Danner
Parcel 009-94-01084